bg sanpham
FM 200 Clean Agent Cylinders (welded) FM 200 Clean Agent Cylinders (welded) The Fire Products FM 200 Fire Extinguishing System uses HFC-227ea extinguishing agent that is stored in the system’s extinguishing agent container(s) until system activation. The container assembly includes a welded cylinder filled with HFC-227ea fluid 889XXX (098,100,103), 910508 Viking FM-200 Fire Suppression System 1.000 đ SoldOut
  • FM 200 Clean Agent Cylinders (welded)

    889XXX (098,100,103), 910508
  • The Fire Products FM 200 Fire Extinguishing System uses HFC-227ea extinguishing agent that is stored in the system’s extinguishing agent container(s) until system activation. The container assembly includes a welded cylinder filled with HFC-227ea fluid

  • Manufacturer: Viking
  • Origin: Germany
  • Download:
    2.17 MB
- Extinguishing agent: HFC-227ea
- Extinguishing agent cylinder UL/FM,VSN 200 type 25, (welded) 22 l, 52 l,106 l, 147 l, 180 l
- Fill ratio:
+ Min. VdS / CE: 0.4 kg/l (25.0 lbs/ft3)
UL / ULC / FM: 0.5 kg/l (31.1 lbs/ft3)
+ Max. VdS: 1.04 kg/l (64.9 lbs/ft3)
CE / UL / ULC / FM: 1.14 kg/l (71.1 lbs/ft3)
- Operating temperature range: -20 °C to +50 °C (-4 °F to 122 °F)
UL / ULC / FM: -18 °C to +50 °C (0 °F to 122 °F)
- Cylinder flled: by a qualifed flling centre steel cylinder (welded) ......according to DOT and TC regulations
- Working pressure: max. 35 bar / 50 °C (507 psi / 122 °F)
- Finish: Federal Red P20750, other colour upon customer request
 

>>> Learn more: Viking FM-200 Fire Suppression System
>>> Learn more: Viking NOVEC 1230 Fire Suppression System
>>> Learn more: Other Prodects

Products in this Category


 
You did not use the site, Click here to remain logged. Timeout: 60 second