bg sanpham
Pilot control manifold CO2-DN15 Pilot control manifold CO2-DN15 The pilot control  manifold  DN 15 may only be used in accordance   with system  approval  in stationary  C02, argon, nitrogen,  IG-55, IG-541 and VSN 1230/200  fire extinguishing systems.  It is used as a pilot control  valve  in the pneumatic activation  of fire extinguishing   systems  or as a C02   extinguishing agent  manifold  for small  design  quantity. 8307XX (78,91), 8308XX (08,33,57,70) Viking NOVEC 1230 Fire Suppression System 1.000 đ SoldOut
  • Pilot control manifold CO2-DN15

    8307XX (78,91), 8308XX (08,33,57,70)
  • The pilot control  manifold  DN 15 may only be used in accordance   with system  approval  in stationary  C02, argon, nitrogen,  IG-55, IG-541 and VSN 1230/200  fire extinguishing systems.  It is used as a pilot control  valve  in the pneumatic activation  of fire extinguishing   systems  or as a C02   extinguishing agent  manifold  for small  design  quantity.

  • Manufacturer: Viking
  • Origin: Germany
  • Download:
    593.49 KB
- Approvals: VdS, UL, UL-C, FM
- Operating  medium: carbon dioxide (C02)  
- Working  pressure: 140 bar (2030 psi)
- Test pressure: 235 bar (3408 psi)
- Temperature  range: -20 °C  to +50 °C  (-4 °F  to +122 °F)
- Connected  voltage: 24 V DC
- Part no.
+ 830778 -DN15 - 2 Branches
+ 830791 - DN15 - 3 Branches
+ 830808 - DN15 - 4 Branches
+ 830833 - DN15 - 5 Branches
+ 830857 - DN15 - 6 Branches
+ 830870 - DN15 - 7 Branches