The Systems Releasing Module will support the following system inputs and outputs:
- One Fusible Link Detection Line
- One Gas Valve Line
- One Remote Pull Station Line
Two windows in the front cover of the Model SRM allow for visual verification of the actuation cartridge presence and the status of the puncture pin mechanism.
The Model SRM can actuate a maximum of three (3) agent cylinders when using the Model BFR-AC-S Nitrogen Activation Cartridge (included with SRM and SRM-D) or five (5) agent cylinders when a Model BFRAC-L Nitrogen Activation Cartridge is installed.