bg sanpham
The manifold selector valve BV DN65/80/100 The manifold  selector valve BV DN65/80/100 The manifold selector valve  BV DN65/80/100 pneumatic is used in accordance with "documentation of special extinguishing systems" in:
- fixed C02- high pressure fire extinguishing systems - argon-,  nitrogen, IG-55-, IG-541 extinguishing systems with Constant Flow (CF)
GABVDN65/80/100 Viking FM-200 Fire Suppression System 1.000 đ SoldOut
  • The manifold selector valve BV DN65/80/100

    GABVDN65/80/100
  • The manifold selector valve  BV DN65/80/100 pneumatic is used in accordance with "documentation of special extinguishing systems" in:
    - fixed C02- high pressure fire extinguishing systems - argon-,  nitrogen, IG-55-, IG-541 extinguishing systems with Constant Flow (CF)

  • Manufacturer: Viking
  • Origin: Germany
  • Download:
    1.95 MB
- ApprovalsICE marking: VdS, UL, UL-C, FM, CTP, CE
- Operating  medium: C02,   argon (IG-01 ),  nitrogen (IG-100), IG-55,   IG-541,   FK-5-1-12,  HFC-227ea
- Working  pressure  I test pressure:
+ Manifold,  selector  valves: 140 bar I 210 bar (2030 psi I 3045 psi)
+ Pneumatic  release  device: 20 to 140 bar I 210 bar  (290 to 2030 psi I 3045 psi)
- Temperature  range: -20 °C to +50 °C (-4 °F  to 122 °F)
- Actuation: 24 V DC
- Flow characteristics (high pressure  selector  valve):
+ DN65: equivalent  length 0.43 m (16.93")
+ DN80: equivalent  length 0.55 m (21.65")
+ DN100: equivalent  length 0.67 m (26.38")
- VSN 1230/200 fire extinguishing systems, maximum number of selector valves:  15.
- In case of fire the selector valve DN65/80/100 is used for flooding selected extinguishing   zones.