The Shuttle Noreturn Valve
886247'
The shuttle non-return valve is used in fixed high pressure C02, argon, nitrogen, IG-55 and IG-541 fire extinguishing systems or in VSN 1230/200 fire extinguishing systems according the system approval.
- Approvals I CE marking: VdS, UL, UL-C, FM, CE - Operating medium: C02 - gaseous - Working pressure: 2 to 140 bar (29 to 2030 psi) - Test pressure: 210 bar (3045 psi) - Rate of pressure rise: min. 3 barfs (43,5 psi/s) - Installation position: feedings only horizontal - Shuttle non-return valves: complies with EN 12094-13 - Part no.: 886247 - 6x1 - 0.25 kg (0.55 lbs)