bg sanpham
FM 200 Clean Agent Cylinders (seamless) FM 200 Clean Agent Cylinders (seamless) The Fire Products FM 200 Fire Extinguishing System uses HFC-227ea extinguishing agent that is stored in the system’s extinguishing agent container(s) until system activation. The container assembly includes a seamless cylinder filled with HFC-227ea fluid  8884XX (63,65,82,84), 8885XX (74,76) Viking FM-200 Fire Suppression System 1.000 đ SoldOut
  • FM 200 Clean Agent Cylinders (seamless)

    8884XX (63,65,82,84), 8885XX (74,76)
  • The Fire Products FM 200 Fire Extinguishing System uses HFC-227ea extinguishing agent that is stored in the system’s extinguishing agent container(s) until system activation. The container assembly includes a seamless cylinder filled with HFC-227ea fluid 

  • Manufacturer: Tyco
  • Origin: Germany
  • Download:
- Extinguishing agent: HFC-227ea
- Min. fll ratio:
+ VdS / CE: 0.4 kg/l (25.0 lbs/ft3)
+ UL / ULC / FM / GL: 0.5 kg/l (31.1 lbs/ft3)
- Max. fll ratio, 25 bar / 42 bar (360 psi / 610 psi):
+ VdS: 1.04 kg/l (64.9 lbs/ft3)
+ CE / GL / UL / ULC / FM: 1.14 kg/l (71.1 lbs/ft3)
- Max. fll ratio, 50 bar (725 psi):
+ VdS: 0.85 kg/l (53.0 lbs/ft3)
+ CE / GL / UL / ULC / FM: 1.05 kg/l (65.5 lbs/ft3)
- Operating temperature range: -20 °C to +50 °C (-4 °F to 122 °F)
UL / ULC / FM ........................-18 °C to +50 °C (0 °F to 122 °F)
- Cylinder flled: by a qualifed flling centre
- Steel cylinder (seamless) ...acc. to directive TPED 2010/35/EC, directive MED 96/98/EC and DOT regulations
- Working pressure: max. 60 bar / 60 °C (870 psi / 140 °F)
- Finish: RAL3000 - flame red other colour upon customer request
(Note: colour, colour type are part of the UL / ULC approval)


>>> Learn more: Viking FM-200 Fire Suppression System
>>> Learn more: Viking NOVEC 1230 Fire Suppression System
>>> Learn more: Other Prodects

 
 

Products in this Category


Part No: 8851xx (89, 91,92)
Part No: 88931X (1, 2, 3)
Part No: 91210X (0, 1, 2)
Part No: 889XXX (098,100,103), 910508
 
You did not use the site, Click here to remain logged. Timeout: 60 second