Eight input Remote Modules Eight input Remote Modules The D7042 and D7042B Addressable Multiplex Eight‐input Remote Modules have eight input loops for conventional contacts that can be used to monitor four‐wire smoke detectors, waterflow contacts, and supervisory sensors. The module must be wired Class B to the multiplex bus of the D7024 or FPD‐7024 Fire Alarm Control Panel (FACP).
 
D7042, D7042B Bosch Conventional Fire Alarm System 1.000 đ SoldOut
  • Eight input Remote Modules

    D7042, D7042B
  • The D7042 and D7042B Addressable Multiplex Eight‐input Remote Modules have eight input loops for conventional contacts that can be used to monitor four‐wire smoke detectors, waterflow contacts, and supervisory sensors. The module must be wired Class B to the multiplex bus of the D7024 or FPD‐7024 Fire Alarm Control Panel (FACP).
     

  • Manufacturer: Bosch
  • Origin: China
  • Download:
    348.08 KB
    159.93 KB
- Has eight Class B (Style B) initiating circuits
- Includes eight UL Listed EOL resistors
- Convenient plastic case (D7042) or red metal fire enclosure (D7042B) for remote mounting
- Easy to install
- Connects to multiplex bus
- Current (alarm and standby): 10 mA at 12 VDC through multiplex bus; 8 mA from option bus --- Battery Calculation Current (alarm and standby): 18 mA
- Voltage (operating): 8 VDC peak minimum bus