Tyco Concealed Pendent Sprinkler TY3539 Tyco Concealed Pendent Sprinkler TY3539 Tyco Concealed Pendent sprinkler TY3539 (Series DS-ECC) 5.6K quick response (3 mm Bulb), Extended Coverage is decorative bulb- type sprinklers featuring a flat cover plate designed to conceal the sprinkler. This type of sprinkler is typically used to provide a sprinkler drop from an unheated attic into an area where aes- thetics is a concern, such as nursing homes, restaurants, and schools.
 
P000103 Dry Sprinklers 1.000 đ SoldOut
  • Tyco Concealed Pendent Sprinkler TY3539

    P000103
  • Tyco Concealed Pendent sprinkler TY3539 (Series DS-ECC) 5.6K quick response (3 mm Bulb), Extended Coverage is decorative bulb- type sprinklers featuring a flat cover plate designed to conceal the sprinkler. This type of sprinkler is typically used to provide a sprinkler drop from an unheated attic into an area where aes- thetics is a concern, such as nursing homes, restaurants, and schools.
     

  • Manufacturer: Tyco
  • Origin: US
  • Download:
- Approvals: UL, C-UL & NYC.
- Maximum Working Pressure: 175 psi (12.1 bar)
- Discharge Coefficient: K = 5.6 GPM/psi½ (80,6 LPM/bar½
- Inlet Thread Connections: 1 inch NPT (ISO 7-R1).
- Adjustment: 1/2 inch (12,7 mm)
- Temperature Ratings
+ 155°F (68°C) Sprinkler with 139°F (59°C) Cover Plate
+ 200°F (93°C) Sprinkler with 165°F (74°C) Cover Plate
- It is intended for use in automatic sprinkler systems designed in accordance with standard installation rules.  The fast response thermal sensitivity rating of TY3539 provides for a quick response extended coverage (QREC) rating up to an 18 ft. x 18 ft. coverage area.
- The separable two-piece design of the Cover Plate and Support Cup Assemblies allows installation of the sprinklers and pressure testing of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protection system and remove sprinklers.

 