Tyco pendent sprinkler TY9226 Tyco pendent sprinkler TY9226 Tyco pendent sprinkler TY9226 (series ESFR-25) is Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 25.2. They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
 
P000058 Storage Sprinklers 1.000 đ SoldOut
  • Tyco pendent sprinkler TY9226

    P000058
  • Tyco pendent sprinkler TY9226 (series ESFR-25) is Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 25.2. They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.
     

  • Manufacturer: Tyco
  • Origin: US/UK
  • Download:
    303.28 KB
- Approvals: UL, C-UL, FM, NFPA13
- Maximum Working Pressure: 175 psi (12,1 bar)
- Discharge Coefficient: K=25.2 GPM/psi½ (362.9 LPM/bar½).
- Pipe Thread Connection: 1 inch NPT (ISO 7-R1).
- Finishes: Natural Brass
- Maximum Coverage Area: 100 ft² (9.3 m²).
- Minimum Coverage Area: 64 ft² (5,8 m²)
- Temperature Ratings:
+ 165°F (74°C) - Frame Color Code: Unpainted
+ 212°F (100°C) - Frame Color Code: White
- Maximum distance between sprinklers is 10ft (3.1m)
- Minimum distance between sprinklers is 8ft (2.44 m).
- TY9226 has been designed to operate at substantially lower-end head pressures, as compared to ESFR Sprinklers having nominal K-factors of 14.0 and 16.8. This feature offers flexibility when sizing system piping, as well as possibly reducing or eliminating the need for a system fire pump.

 