- For applications in poured concrete ceiling/floor assemblies, a unique Installation Cup is used to form the recessed cavity into which the FSC Sprinkler is installed.
- For suspended ceiling applications, a Dust Cap is used to protect the FSC Sprinkler above the ceiling panel.
- The flush design is made aesthetically appealing by concealing the deflector and other operating parts above the link assembly
- Approvals: VdS
- Maximum Working Pressure: 175 psi (12,1 bar)
- Discharge Coefficient: K=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)
- Inlet Thread Connection: 3/8 inch NPT
- Temperature Ratings: 165°F (74°C)
- Finish: Sprinkler: White/Gray and Escutcheon: White/Gray